Ex d IIC Flame proof Control Boxes Type CCA
Products > Ex d Systems

Description
Flame proof boxes are ideally suitable for integration of control and regulation devices directly in a potentially explosive atmosphere. Exepd offers you a complete product range of terminal and control boxes.
These are certified according to Directive 2014/34/EU for application both in potentially explosive atmospheres classified as Zone 1 and in areas with combustible dusts classified as Zone 21. The flame proof boxes are individually equipped with the respective devices, wired according to circuit diagram and equipped with the appropriate cable glands according to customer requirements.
Combination of specially certified control, signalling and indication elements is realised by integration in a conventional Ex e housing within the scope of Exepd certification. Thanks to processes adapted to customized special solutions and flexible partners, Exepd is able to realise short delivery periods for your projects.
- Installation of terminals
- Integration of control and signalling elements
- Integration of switching, regulation and control elements
- Integration of programmable logic controllers
- Installation of indication elements behind an inspection glass
Description
Typ CCA
Ex d terminal and control boxes are used for the accommodation of switching, and signaling control elements in machines or as peripheral control points in a system.
The terminal and control boxes of type CCA are certified according to Directive 2014/34/EU for zone 1 (IIC) and for zone 21. They are individually equipped with customized elements, wired according to a circuit diagram and equipped with the appropriate cable glands.
In cooperation with our partners we guarantee short delivery periods and fair pricing for the Ex d control units.
Technical Data

Material: | Aluminium |
Color: | outside: grey, RAL 7000 inside: Pur orange, RAL 2004 anti-condensate coating |
Protection: | max. IP 66/67 |
Max. possible ambiente temperature: | -50°C to +80°C |
Design: | with screwed lid |
Type of protection
II 2G Ex d IIC T6 - T4 Gb II 2(1) Ex d [ia] IIC T6 Gb II 2D Ex tb IIIC T85°C - T135°C Db | ||||||
| ATEX | |||||
Zone | 0 | 1 | 2 | 20 | 21 | 22 |
usable in | x | x | x | x |
Documentation

Selection table
Externals dimension | Internal dimensions | Dimensions assembly | internal space | ||||||||||||
Typ | A mm | B mm | C mm | ØD mm | Q mm | E mm | F mm | G mm | ØH mm | I mm | L mm | M mm | N mm | ØO mm | Gewicht kg |
CCA 0 | 150 | 150 | 109 | 130 | 195 | 122 | 122 | 90 | 102 | 175 | 125 | 8 | 80 | 95 | 2,85 |
CCA 1 | 165 | 165 | 123 | 145 | 210 | 137 | 137 | 100 | 117 | 190 | 140 | 8 | 90 | 110 | 3,50 |
CCA 2 | 190 | 190 | 147 | 166 | 235 | 160 | 160 | 122 | 135 | 215 | 165 | 8 | 110 | 125 | 5,60 |
CCA 3 | 225 | 225 | 175 | 200 | 290 | 193 | 223 | 145 | 161 | 260 | 220 | 10 | 130 | 156 | 10,35 |
CCA 4 | 270 | 305 | 205 | 240 | 330 | 238 | 273 | 160 | 198 | 300 | 270 | 10 | 145 | 190 | 14,60 |
CCA 5 | 300 | 340 | 237 | 270 | 360 | 364 | 304 | 190 | 225 | 330 | 300 | 10 | 175 | 217 | 21,30 |