Description

Flame proof boxes are ideally suitable for integration of control and regulation devices directly in a potentially explosive atmosphere. Exepd offers you a complete product range of terminal and control boxes.
These are certified according to Directive 2014/34/EU for application both in potentially explosive atmospheres classified as zone 1 and in areas with combustible dusts classified as zone 21. The flame proof boxes are individually equipped with the respective devices, ired according to circuit diagram and equipped with the appropriate cable glands according to customer requirements.
Combination of specially certified control, signalling and indication elements is realised by integration in a conventional Ex e housing within the scope of Exepd certification. Thanks to processes adapted to customized special solutions and flexible partners, Exepd is able to realise short delivery periods for your projects.

  • Installation of terminals
  • Integration of control and signalling elements
  • Integration of switching, regulation and control elements
  • Integration of programmable logic controllers
  • Installation of indication elements behind an inspection glass


Description
Typ CCF
Ex d terminal and control boxes are used for the accommodation of switching, and signaling elements in machines or as peripheral control points in a system.
The terminal and control housings of type CCF are certified according to Directive 2014/34/EU for zone 1 (IIB) and for zone 21. They are individually equipped with customized elements, wired according to a circuit diagram and equipped with the appropriate cable glands.
In cooperation with our partners we guarantee short delivery periods and fair pricing for the Ex d control units.

Technical data
Material:Aluminium
Color:outside: grey, RAL 7000
inside: pur orange, RAL 2004
anti-condensate coating
Protection:IP 66
(Depending on size  and design)
Max. application temperature:
-50°C to +60°C

Type of protection
II 2G Ex d IIB+H2 T6-T3 Gb
II 2G Ex d [ia] IIB+H2 T6 Gb
II 2D Ex tb IIIC T85°C-T200°C Db
II 2D Ex tb [ia] IIIC 85°C-T200°C Db

ATEX

Zone

0

1

2

20

21

22

usable in


x x x x

Documentation
Certification / ApprovalsINERIS14ATEX0008X




IECEx INE 13.0065X











Data sheet





Dimensions / weight






Declaration of Conformity







operating manual










Selection table


Type
Ext. Dim. in mm
Int. Dim. in mm
Installation dimension in mm
Weigth
in kg
A
B
C
a
b
c
c'
D
E
F
G
H
I
CCF 0G1501501279393969410460M614071603,2
CCF 1G150200127931439694104110M614071604,1
CCF 2G200250150140190124122154160M619072106,8
CCF 3G250300150175225117112185180M6230925510,6
CCF 3AG250300200175225167162185180M6230925511,9
CCF 4G250350150175275117112185230M6230925512,0
CCF 4AG250350200175275167162185230M6230925513,3
CCF 5G300400200218318164159225275M8275930018,0
CCF 5AG300400250218318214209225275M8275930020,0
CCF 6G300450200218368164159225325M8275930020,0
CCF 6AG300450250218368214209225325M8275930022,5
CCF 7G400500200305405152150315350M103701140031,0
CCF 7AG400500250305405202200315350M103701140034,0
CCF 8G350550200255455152150265400M103201135031,0
CCF 8AG350550250255455200200265400M103201135034,0
CCF 9G400600200300500145143315450M103701140038,0
CCF 9AG400600250300500195193315450M103701140043,0
CCF 10G450650200356548145141360500M104201145049,0
CCF 10AG450650250356548195191260500M104201145055,0
CCF 10BG450650300356548245241360500M104201145061,5
CCF 11G500700250386586194183395520M124651350068,0
CCF 11AG500700300386586244233395520M124651350076,0
CCF 11AG500700350386586294283395520M124651350084,0
CCF 12G550750250436636190180445570M125151355082,0
CCF 12AG550750300436636240230445570M125151355090,0
CCF 12BG550750350136636290280445570M125151355098,0
CCF 13G200600140120520105100135470M6180920515,5
CCF 14G220750175140670130125150610M8200922524,0
CCF 16G670920330550800250245560650M1666016700134
CCF 16AG670920390550800310303560650M1666016700145
CCF 16BG670920450550800370362560650M1666016700162
CCF 20BG450450470356356405398360300M104201145051,0

Control and signal elements
for Ex d control cabinets

 
Selector switch with turning knob
(also suitable for potentiometers)

Switching positions 0-1, 1-0-2, locked and non-locked

For switches from 10 to 63A


 
Pushbutton
 
With normally-closed and normally-open switching contacts
Switching cap.:
AC15 24V/10A; 130V/6.5A; 230V/4A; 400V/2.5A
DC13 24V/1.5A; 110V/0.5A

 

 
Emergency-stop push button

With normally-closed and normally-open switching contacts
Switching cap.:
AC15 24V/10A; 130V/6.5A; 230V/4A; 400V/2.5A
DC13 24V/1.5A; 110V/0.5A
 

 
Lockable emergency-stop push button

With normally-closed and normally-open switching contacts
Switching cap.:
AC15 24V/10A; 130V/6.5A; 230V/4A; 400V/2.5A
DC13 24V/1.5A; 110V/0.5A
 

 
Key switch

With normally-closed and normally-open switching contacts
Switching cap.:
AC15 24V/10A; 130V/6.5A; 230V/4A; 400V/2.5A
DC13 24V/1.5A; 110V/0.5A
 

 
Indication light
 
Available in colours white, green, red, yellow and blue
For voltage rating: 12-24VDC, 240VAC and 440VAC
 
Pushbutton element
For actuation of actuators inside the Ex d housing
 
Other actuation elements and windows on request.